Hero Banner

Welcome to Our Company

Explore the best products from top brands

Control & Monitoring: DCS, ESD. SCADA, HMI, PLC

All products

Q00JCPU

$261.00

Basic model QCPU Q00JCPU


• Estimated Lead Time : In stock. Usually ships in 3-5 working days.

• Manufacturer : Mitsubishi Electric

• Q00JCPU

• Basic model QCPU Q00JCPU

• control method : Stored program iteration operation

• Input / output control method : Refresh method (Direct access input / output possible by specifying direct access input / output (DX, DY))

• Programming language Sequence control language : Relay symbol word, logic symbolic word, MELSAP 3 (SFC), MELSAP-L, function block, structured text (ST)

• processing speed Sequence instructions LD X 0 : 200 ns

• MOV D 0 D 1 : 700 ns

• Constant scan : 1 ~ 2000 ms (Can be set in 1 ms increments)

• Program capacity : 8K steps (32K bytes)

• Memory capacity Program memory (drive 0) : 58 KB

• Standard ROM (Drive 4) : 58 KB

• Maximum number of stored files Program memory : 6

• Standard ROM : 6

• Intelligent functional unit Parameter Maximum setting number Initial setting : 512 pieces

• refresh : 256 pieces

• Number of input / output devices : 2048 points (X / Y 0 to 7 FF)

• Number of input / output points : 256 points (X / Y 0 to FF)

• Number of device points Internal relay [M] : Default 8192 points (M0 to 8191) (changeable)

• Latch relay [L] : Default 2048 points (L0 to 2047) (changeable)

• Link relay [B] : Default 2048 points (B 0 - 7 FF) (changeable)

• Timer [T] : Default 512 points (T0 to 511) (Shared with low-speed timer / high-speed timer) (Changeable) Low-speed timer / high- speed timer specified by instruction Low-speed timer / high-speed timer measurement unit is set by parameter (low-speed timer: 1 to 1000 ms, 1 ms increment, default 100 ms) (High-speed timer: 0.1 to 100.0 ms, 0.1 ms increments, default 10.0 ms)

• Integration timer [ST] : Default 0 point (Shared with low speed integration timer / high speed integration timer) (Changeable) Low speed integration timer / high speed integration timer specified by instruction Set the measurement unit of low speed integration timer / high speed integration timer by parameter (low speed integration timer: 1000 ms, 1 ms increment, default 100 ms) (High-speed integration timer: 0.1 to 100.0 ms, 0.1 ms increments, default 10.0 ms)

• Counter [C] : Normal counter: default 512 points (C 0 to 511) (changeable) Interrupt counter: maximum 128 points (default 0 point, set by parameter)

• Data register [D] : Default 11136 points (D0 to 11135) (changeable)

• Link register [W] : Default 2048 points (W 0 to 7 FF) (changeable)

• Annunciator [F] : Default 1024 points (F0 to 1023) (changeable)

• Edge relay [V] : Default 1024 points (V 0 to 1023) (changeable)

• Link special relay [SB] : 1024 points (SB 0 to 3 FF) (Device number is fixed)

• Link special register [SW] : 1024 points (SW 0 to 3 FF) (the number of device points is fixed)

• Step relay [S] : 2048 points (S 0 ~ 127 / block) (Device number is fixed)

• Index register [Z] : 10 points (Z 0 ~ 9) (Device number is fixed)

• Pointer [P] : 300 points (P 0 ~ 299) (Device number is fixed)

• Interrupt pointer [I] : 128 points (I 0 to 127) ( Number of device points is fixed) Periodic interval of system interrupt pointer I 28 to 31 can be set by parameter. (2 to 1000 ms, 1 ms increments) Default I 28: 100 ms, I 29: 40 ms, I 30: 20 ms, I 31 : 10 ms

• Special relay [SM] : 1024 points (SM 0 ~ 1023) (Device number is fixed)

• Special register [SD] : 1024 points (SD 0 ~ 1023) (Device number is fixed)

• Function input [FX] : 16 points (FX 0 to F) (Device number is fixed)

• Function output [FY] : 16 points (FY 0 to F) (the number of device points is fixed)

• Function register [FD] : 5 points (FD 0 ~ 4) (Device number is fixed)

• Link direct device : J鈻♀枴 X鈻♀枴, J鈻♀枴 Y鈻♀枴, J鈻♀枴 SB鈻♀枴, J鈻♀枴 SB鈻♀枴, J鈻♀枴 SB鈻♀枴, J鈻♀枴 SW鈻♀枴, J鈻♀枴 SW??Device specification form for directly accessing the link device of the network unit??/p>

• Intelligent functional unit device : Device specification that directly accesses buffer memory of intelligent function module Format: U鈻♀枴 G鈻♀枴

• Latch (power outage hold) range : L 0 to 2047 (default 2048 points) [latch range can be set for B, F, V, T, ST, C, D, W]

• RUN / PAUSE contact : One point of each RUN / PAUSE contact can be set from X 0 to 7 FF

• Clock function : Year, month, day, hour, minute, second, day of the week (leap year automatic discrimination) accuracy: -3.20 ~ + 5.27s (. TYP + 1.98s) / d at 0 掳C accuracy: -2.57 ~ + 5.27s (TYP + . 2.22 s) / d at 25 掳 C. Accuracy: -11.68 to +3.65 s (TYP. -2.64 s) / d at 55 掳 C.

• Allowable momentary power failure time : Within 20 ms (AC 100 V or more)

• DC 5 V Internal current consumption : 0.26 A

• External dimensions Height (H) : 98 mm

• Width (W) : 244.4 mm

• Depth (D) : 98 mm

• mass : 0.66 Kg

• Power supply part :

• Input supply voltage : AC 100 to 240 V (-15% to + 10%)

• Input frequency : 50/60 Hz 卤 5%

• Input voltage distortion ratio : Within 5%

• Input maximum apparent power : 105VA

• Inrush current : 40 A within 8 ms

• Rated output current DC 5V : 3A

• Overcurrent protection DC 5V : 3.3 A or more

• Overvoltage protection DC 5V : 5.5 to 6.5 V

• efficiency : 65% or more

• Withstand voltage : Input . LG collective and output . FG all at once AC 2300 V / 1 min (altitude 0 to 2000 m)

• Insulation resistance : Input . LG collective and output . Between FG batch, input batch and LG, batch output and FG: 500 MV DC insulation resistance meter 10 M惟 or more

• Operation indication : LED display (normal: green lighting, abnormal: off, CPU part "POWER" LED)

• fuse : Built-in (user replaceable)

• Contact output unit : None

• External wiring connection method : Screw terminal block (M3.5 screw)

• Base part :

• Number of input / output units : Five

• Applicable unit : MELSEC-Q series unit

• Operating ambient temperature : 0 to 55 掳 C

• Storage ambient temperature : -25 to 75 掳 C

• Ambient operating humidity : 5 to 95% RH, non condensing

• Storage ambient humidity : 5 to 95% RH, non condensing

• Anti-vibration Meets JIS B 3502, IEC 61131-2 When there is intermittent vibration : Frequency: 5 to 8.4 Hz, One amplitude: 3.5 mm Frequency: 8.4 to 150 Hz, Constant acceleration: 9.8 m / s 2 Sweep count: 10 times in X, Y, Z directions

• When there is continuous vibration : Frequency: 5 to 8.4 Hz, One amplitude: 1.75 mm Frequency: 8.4 to 150 Hz, Constant acceleration: 4.9 m / s 2

• Impact resistance : Meets JIS B 3502, IEC 61131-2 (147 m / s 2 , 3 times in each of X, Y and Z directions)

• Use atmosphere : No corrosive gas

• Use elevation : 0 to 2000 m

• Installation location : In the control panel

• Over voltage category : II or less

• Pollution degree : 2 or less

• Device class : Class I

• Shipping Weight : 1.7 Kg